GB200 NVL72 vs HGX B200

Same GPU, different system: a 72-GPU NVLink rack against an 8-GPU server.

The difference

Both use the Blackwell GPU. GB200 NVL72 pairs it with Grace CPUs and joins 72 GPUs in one NVLink domain; HGX B200 joins 8. Per GPU, the GB200 runs slightly faster (5 vs 4.5 dense FP8 PFLOPS) with 186 GB against 180 GB. It is liquid-cooled only, at about 120 kW per rack.

Side by side

Per GPUHGX B200GB200 NVL72GB200 NVL72 / HGX B200
Architecture, releasedBlackwell, Early 2025Blackwell, Early 2025
Memory180 GB (1.4 TB per 8-GPU board)186 GB (13.4 TB per rack)1.03x
Memory bandwidth8 TB/s8 TB/s (576 TB/s per rack)1.00x
BF16, dense TFLOPS2,2502,5001.11x
FP8, dense TFLOPS4,5005,0001.11x
FP4, dense TFLOPS9,00010,0001.11x
FP64 (Tensor / matrix), TFLOPS37401.08x
Max power per GPU1,000 W air-cooled, 1,200 W liquidNot published per GPU; about 120 kW per rack
Power per 8 GPUsAbout 14 kWAbout 120 kW per 72-GPU rack (13.3 kW per 8 GPUs)0.95x
GPU-to-GPU linkNVLink 5, 1.8 TB/s per GPUNVLink 5, 1.8 TB/s per GPU, 130 TB/s per rack
Scale-up domain8 GPUs (HGX board)72 GPUs (one NVLink domain)
Form factor, coolingSXM module, 8-GPU HGX board; air or liquidGrace Blackwell Superchip (1 Grace CPU + 2 GPUs), 72-GPU rack; liquid only
Price per GPU, October 2026$45,000-$58,750 (New 8-GPU node, per GPU)-
Launch price reported in the press$30,000 to $40,000 per unit, per NVIDIA’s CEO (2024)$60,000 to $70,000 per Superchip (1 CPU + 2 GPUs); $3M per NVL72 rack, HSBC (2024)
Residual band, 2027 (conservative)40-54% of original price-

Tensor Core figures are dense. Prices as of October 2026.

Sources: American Compute, NVIDIA, Managed GPUs (American Compute), CNBC, Tom's Hardware.

The difference is the system

The difference is the system, not the chip. In an HGX B200, eight GPUs share NVLink on one board, and anything larger crosses the network. In GB200 NVL72, switch trays join all 72 GPUs at 130 TB/s of aggregate bandwidth, so a model split across the rack talks over NVLink.

Power, cooling and resale

An NVL72 rack needs a liquid-cooled site. It draws roughly 120 kW, and past about 40 kW per rack air cooling stops working. An HGX B200 server draws about 14 kW and goes into far more data centers, so it has more buyers when it changes hands.

We publish no separate rack-scale band. Our residual report groups GB200 with B200 by technology age; the B200 conservative band is 40-54% of original price in 2027.

Sources: NVIDIA, American Compute, Managed GPUs (American Compute).

Residual value and appraisals

YearHGX B200GB200 NVL72
202659-67%-
202740-54%-
202830-42%-
202916-26%-
20306-11%-